All calculators / Heating & cooling
What size furnace do I need?
Most furnaces are bigger than the house needs. Enter your house and climate to see the heat loss and the smallest furnace that covers it.
Replacing an old unit? Check how old it is first.
40,000 Btu/h furnace
Your heat loss is about 33,300 Btu/h at 15°F. At 96% AFUE, a 40,000 Btu/h (input) furnace delivers 38,400 Btu/h, which covers it.
- If the furnace also carries the AC coil, the blower must move enough air for the AC tonnage (about 400 CFM per ton).
- This is an estimate, not an ACCA Manual J.
How we got there
| Heating design temperature | 15°F | 55°F below a 70°F room |
|---|---|---|
| Heat loss: walls | 5,600 Btu/h | |
| Heat loss: ceiling | 5,500 Btu/h | |
| Heat loss: floor | 3,300 Btu/h | |
| Heat loss: windows | 8,250 Btu/h | |
| Heat loss: air | 6,340 Btu/h | |
| Heat loss: ducts | 4,350 Btu/h | in an unconditioned attic or crawlspace |
| Heating load | 33,300 Btu/h | at the design temperature |
| Furnace efficiency (AFUE) | 96% | |
| Recommended furnace | 40,000 Btu/h input | 38,400 Btu/h output, 115% of the load |
What to look for
- 40,000 Btu/h input, 95%+ AFUE, two-stage or modulating
- Examples: Goodman GMVM97, Carrier Performance 59TP6, Trane S9V2, Lennox SL280V
Examples only, not endorsements: model names checked 2026-11-26. Confirm the exact capacity on the spec sheet before you buy. We earn nothing from these.
Input, output and AFUE
Furnaces are sold by input: the Btu/h of gas they burn. What heats the house is output, which is input × AFUE. A 60,000 Btu/h furnace at 96% puts out 57,600 Btu/h; at 80% it puts out 48,000.
The size that matters is the heat loss on your heating design day, the temperature that only the coldest few hours of a typical year fall below. The calculator adds up the loss through walls, ceiling, floor, windows and air leaks, plus ducts in unheated space, and picks the smallest standard input whose output covers it.
A furnace much bigger than the loss short-cycles, makes the house swing between too warm and too cool, and is louder. Manual S guidance caps furnace output at 140% of heat loss. If the smallest size is above that, a two-stage or modulating furnace runs on low fire most of the time.
If the furnace also runs the AC
The furnace blower moves the air for the AC coil too. Cooling needs about 400 cubic feet per minute per ton, so a 3-ton AC needs a blower rated for about 1,200 CFM. A small furnace with a big AC can need a larger blower cabinet. Check both numbers with the installer.
Replace or repair?
Gas furnaces typically last 15 to 25 years. The build date is in the serial number on the rating plate. Find out how old your current unit is on Serial Age Finder, then size the replacement here.
Questions
What size furnace for a 2,000 sq ft house?
Usually 40,000 to 80,000 Btu/h input, depending on climate and insulation. In Chicago an average 2,000 sq ft house loses about 40,000 to 45,000 Btu/h on a design night, so a 60,000 Btu/h, 96% furnace covers it. The old rule of 50 Btu/h per square foot would say 100,000.
Is it bad to have a furnace that's too big?
It works, but it short-cycles, heats unevenly and is noisier. It also costs more. If your old furnace never ran long cycles on cold days, it was probably oversized.
Should I pick 80% or 96% AFUE?
In zones 4 and colder a condensing (95%+) furnace usually pays back. It needs PVC venting and a condensate drain. In the South, where the furnace runs a few weeks a year, 80% can make sense.
How big of a furnace do I need?
One whose output covers your heat loss on the coldest design night, without going more than 40% over. For an average 2,000 sq ft house in a cold climate that is about 40,000 to 45,000 Btu/h of output, so a 60,000 Btu/h input condensing furnace.
Sources
Method checked 2026-11-26. Full formulas on the methodology page.