What size mini-split do I need?
Mini-splits come in 6,000 to 36,000 Btu/h heads. Enter the space and climate to get the size that covers both summer cooling and winter heating.
Replacing an old unit? Check how old it is first.
6,000 Btu/h mini-split
This 400 sq ft room needs about 6,100 Btu/h of cooling and 6,000 Btu/h of heat at 15°F. A 6,000 Btu/h (0.50-ton) unit is the nearest standard size.
- Heating on the design night needs 6,000 Btu/h. Pick a hyper-heat / cold-climate model rated near full output at 15°F, or keep other heat in the room.
How we got there
| Heating design temperature | 15°F | 55°F below a 70°F room |
|---|---|---|
| Heat loss: walls | 1,290 Btu/h | |
| Heat loss: ceiling | 1,100 Btu/h | |
| Heat loss: floor | 660 Btu/h | |
| Heat loss: windows | 1,650 Btu/h | |
| Heat loss: air | 1,270 Btu/h | |
| Heating load | 6,000 Btu/h | at the design temperature |
| Cooling design temperature | 92°F | 17°F above a 75°F room |
| Heat gain: walls | 630 Btu/h | |
| Heat gain: ceiling | 1,140 Btu/h | |
| Heat gain: windows | 2,660 Btu/h | conduction + sun through glass |
| Heat gain: people | 460 Btu/h | |
| Heat gain: appliances | 400 Btu/h | |
| Heat gain: air | 200 Btu/h | |
| Heat gain: humidity (latent) | 650 Btu/h | |
| Cooling load | 6,100 Btu/h | 0.5 tons |
| Recommended size | 6,000 Btu/h | 0.50 tons |
What to look for
- Single-zone 6,000 Btu/h ductless heat pump
- DIY pre-charged: MRCOOL DIY 4th/5th Gen, Pioneer WYS/Diamante
- Installed, cold climate: Mitsubishi M-Series Hyper-Heat (MSZ-FS / GL), Fujitsu Halcyon XLTH, Daikin Aurora
Examples only, not endorsements: model names checked 2026-11-26. Confirm the exact capacity on the spec sheet before you buy. We earn nothing from these.
Why the 20 Btu per square foot chart oversizes
Most mini-split charts multiply floor area by 20 to 30 Btu/h. That puts a 400 sq ft bedroom at 8,000 to 12,000 Btu/h whatever the climate or walls. An interior room with one outside wall in a mild climate can need half that.
Oversizing a mini-split is less harmful than oversizing central air because inverter units slow down, but each model has a minimum speed. If the load is below it, the unit cycles on and off and dehumidifies poorly. The calculator works out the room's heat gain and loss from its outside walls, windows, ceiling and climate, then picks the nearest head size.
Heating with a mini-split
A mini-split is a heat pump. Rated capacity is measured at 47°F for heating, and output drops as it gets colder. Hyper-heat or cold-climate models (Mitsubishi Hyper-Heat, Fujitsu XLTH, Daikin Aurora and others) keep most of their rating at 5°F. If the calculator warns that heating is close to the unit's size, choose one of those or keep another heat source in the room.
Circuit and install
Most 9,000 to 12,000 Btu/h units run on a 15 or 20 A, 240 V circuit; 18,000 to 24,000 Btu/h units on 20 to 30 A. Some small units run on 120 V. The breaker and wire come from the outdoor unit's nameplate (MCA and MOCP); the wire size calculator takes those numbers.
Replace or repair?
Mini-splits usually last 15 to 20 years. The build date is in the serial number on the rating plate. Find out how old your current unit is on Serial Age Finder, then size the replacement here.
Common questions, worked out
Questions
What size mini-split for 500 sq ft?
Usually 9,000 to 12,000 Btu/h in a mixed climate with average insulation; 12,000 to 18,000 if it is sunny, poorly insulated, or a garage. See the worked answer for 500 sq ft.
Can one mini-split heat a whole house?
An open-plan, well-insulated small house, sometimes. Heat doesn't move well through doorways, so closed bedrooms usually need their own head or a ducted unit.
Should I round up?
Round to the nearest standard size, and up only if the result is close to the next size or the room has big west windows. Inverter units handle a modest oversize better than single-speed ones.
Sources
Method checked 2026-11-26. Full formulas on the methodology page.