All calculators / Electrical
What size wire for a subpanel or service?
Enter the subpanel's breaker and the distance. You get the feeder size in copper or aluminum, the voltage drop, and the ground, using the full 75°C rating subpanel feeders are allowed.
1 AWG aluminum feeder, 100 A breaker
A 100 A subpanel feeder needs at least 1 AWG aluminum SER for a 50 ft run, with a 6 AWG ground.
- Feeders to a subpanel need four wires (two hots, neutral, ground), and the neutral and ground must be separated in the subpanel.
- A subpanel feeder uses the full 75°C ampacity. The 83% rule (NEC 310.12) applies only to the service or main feeder of a dwelling, not to subpanels.
- The 75°C column only applies if the breaker, the appliance and every terminal are rated 75°C. NM-B (Romex) is always 60°C.
- Aluminum: use AL-rated lugs, antioxidant paste, and torque to spec. We never suggest aluminum smaller than 6 AWG.
- Wiring is a fire risk when it's wrong. Most places require a permit; have a licensed electrician confirm the wire, breaker and terminations before anything is energized.
How we got there
| Feeds | A subpanel | full 75°C ampacity; the 83% rule does not apply |
|---|---|---|
| Circuit | 100 A circuit | 240 V |
| Load | 100.0 A | |
| Breaker | 100 A double-pole | next standard size up |
| Wire type | SER / feeder cable, 75°C terminals | 75°C ampacity column |
| Smallest wire for the breaker | 1 AWG aluminum | 100 A (NEC 310.16) |
| Voltage drop over 50 ft | 0.8% | 2.0 V at 80.0 A |
| Equipment ground | 6 AWG aluminum | NEC 250.122 |
What to look for
Examples only, not endorsements: model names checked 2026-11-26. Confirm the exact capacity on the spec sheet before you buy. We earn nothing from these.
Feeder rules
A subpanel feeder is sized like any circuit: the conductors must carry at least the feeder breaker's rating. Feeder cable (SER) and conductors in conduit use the 75°C column of NEC Table 310.16 when the panel lugs and breaker are rated 75°C, which nearly all are.
The well-known "83% rule" that lets a 200 A service use 4/0 aluminum comes from NEC 310.12. It applies only to the service or main feeder that carries a whole dwelling's load, not to a subpanel feeder. A 100 A subpanel therefore needs 1 AWG aluminum or 3 AWG copper, not 2 AWG aluminum.
Subpanels need four conductors: two hots, a neutral and an equipment ground, with the neutral bar isolated from the enclosure. A subpanel in a detached garage or shop also needs its own grounding electrode and a disconnect.
Common questions, worked out
Questions
What size wire for a 100 amp subpanel?
1 AWG aluminum or 3 AWG copper at 75°C, for runs up to roughly 100 ft; longer runs go up a size for voltage drop. Ground: 6 AWG aluminum or 8 AWG copper. See the worked answer.
What size wire for a 60 amp subpanel?
6 AWG copper or 4 AWG aluminum at 75°C for typical runs, with a 10 AWG copper or 8 AWG aluminum ground.
Sources
Method checked 2026-11-26. Full formulas on the methodology page.