What size generator do I need?
Tick what has to run during an outage. The size is everything's running watts plus the start-up surge of the one biggest motor, not every surge added together.
4,500 W portable generator
You need about 3,105 W running and 4,605 W at the moment the refrigerator starts. A generator with about 4,500 running watts (5,625 starting) covers that with headroom.
- Adding every appliance's starting watts gives 7,180 W. Some calculators do that, but appliances don't all start in the same second; the running total plus the largest surge (4,605 W) is the standard method.
- Never back-feed through a dryer outlet. Connect through a transfer switch or interlock, and run the generator outdoors at least 20 ft from doors and windows: carbon monoxide kills.
How we got there
| Refrigerator | 700 W running | 2,200 W to start |
|---|---|---|
| 1/2 hp sump pump | 1,050 W running | 2,150 W to start |
| Gas furnace blower (1/2 hp) | 875 W running | 2,350 W to start |
| 20 LED bulbs | 200 W running | 200 W to start |
| TV + streaming box | 250 W running | 250 W to start |
| Modem + router | 30 W running | 30 W to start |
| All running together | 3,105 W | |
| Largest single start-up surge | +1,500 W | Refrigerator, starting while everything else runs |
| Peak you must cover | 4,605 W | running total + the one largest surge |
| Headroom on running watts | 10% | so the engine isn't at full load for hours |
| Recommended size | 4,500 W running, 5,625 W starting |
What to look for
- About 4,500–5,000 running watts: Champion 5500 Dual Fuel, Westinghouse WGen5300, Generac GP6500
- Add: a transfer switch or panel interlock + inlet box, installed by an electrician
Examples only, not endorsements: model names checked 2026-11-26. Confirm the exact capacity on the spec sheet before you buy. We earn nothing from these.
Running watts and starting watts
Every appliance has running watts, what it draws once it is going, and motors also have starting watts: a surge for a second or two while the motor spins up. A refrigerator runs on about 700 W but can pull 2,200 W to start.
A generator has to cover everything that is running plus one motor starting. Motors rarely start in the same second, so you add the running watts of everything, then add the biggest single surge (starting minus running) on top. Some manufacturer calculators add every starting wattage together, which can double the size and the price.
Portable, inverter or standby
| Type | Typical size | Fits |
|---|---|---|
| Inverter portable | 2,000–4,500 W | Fridge, lights, internet, CPAP, phones; quiet, clean power for electronics |
| Open-frame portable | 5,000–12,000 W | Add a furnace blower, well pump or window AC; needs a 240 V outlet for well pumps |
| Air-cooled standby | 10–26 kW | Most or all of a house, starts by itself within seconds of an outage |
Portables connect to the house through a transfer switch or a panel interlock with an inlet box, installed by an electrician. Standby units come with an automatic transfer switch.
Common questions, worked out
Questions
What size generator to run a house?
To keep the essentials going (fridge, freezer, furnace blower, sump or well pump, lights, internet), most houses need 5,000 to 9,500 running watts. Running central AC and an electric water heater as well takes a 20 to 24 kW standby unit. See the worked answer.
What size generator to run a refrigerator?
A 2,000 to 2,500 W inverter generator runs a typical refrigerator: about 700 W running and up to 2,200 W at start-up. See the worked answer for a fridge and freezer together.
Can I plug the generator into a dryer outlet?
No. A double-male cord back-feeds the utility line and can kill a lineworker or start a fire. Use a transfer switch or an interlock kit.
Where can the generator go?
Outdoors, at least 20 ft from the house, with the exhaust pointed away from doors and windows. Never in a garage, even with the door open. Install battery carbon monoxide alarms.
How big of a generator do I need?
Add up the running watts of what must run in an outage and add the start-up surge of the single biggest motor. For a refrigerator, furnace blower, sump pump, lights and internet that is about 3,100 W running and 4,600 W at start-up, so a portable rated around 4,500 running watts. With central air you are into 18 to 22 kW standby units.
Sources
Method checked 2026-11-26. Full formulas on the methodology page.