All calculators / Electrical
What size wire and breaker do I need?
Pick the appliance or enter the amps. You get the breaker, the smallest legal wire for your cable type, the voltage drop over the run, and the ground wire, with the NEC table behind each.
10 AWG copper on a 30 A breaker
An electric dryer on a 30 A breaker needs at least 10 AWG copper NM-B for a 50 ft run, with a 10 AWG ground.
- Appliance nameplates and install manuals set the breaker size (MOCP). Where they differ from this page, the nameplate wins.
- Wiring is a fire risk when it's wrong. Most places require a permit; have a licensed electrician confirm the wire, breaker and terminations before anything is energized.
How we got there
| Circuit | Electric dryer | 240 V |
|---|---|---|
| Load | 24.0 A | |
| Breaker | 30 A double-pole | typical; use the nameplate or manual |
| Wire type | NM-B (Romex) cable | 60°C ampacity column |
| Smallest wire for the breaker | 10 AWG copper | 30 A (NEC 310.16, 240.4(D)) |
| Voltage drop over 50 ft | 1.2% | 3.0 V at 24.0 A |
| Equipment ground | 10 AWG copper | NEC 250.122 |
What to look for
Examples only, not endorsements: model names checked 2026-11-26. Confirm the exact capacity on the spec sheet before you buy. We earn nothing from these.
How the wire is chosen
The breaker protects the wire, so the wire must be rated for at least the breaker's amps. NEC Table 310.16 lists how many amps each gauge of copper or aluminum carries, in three temperature columns.
NM-B (Romex) and UF cable are limited to the 60°C column. Conductors in conduit and SER cable can use the 75°C column only if the breaker and the appliance terminals are rated 75°C, which most modern ones are.
Small wires have a further cap in NEC 240.4(D): 14 AWG copper may be protected at no more than 15 A, 12 AWG at 20 A and 10 AWG at 30 A, whatever the table says.
Then voltage drop: long runs waste voltage, so if more than 3% is lost the calculator goes up a size.
Common circuits
| Circuit | Breaker | Copper NM-B | Copper THHN, 75°C |
|---|---|---|---|
| 15 A lighting and outlets | 15 A | 14 AWG | 14 AWG |
| 20 A kitchen, bath, laundry | 20 A | 12 AWG | 12 AWG |
| Electric dryer | 30 A | 10 AWG | 10 AWG |
| Electric range | 40–50 A | 8–6 AWG | 8 AWG |
| 4,500 W water heater | 30 A | 10 AWG | 10 AWG |
| 48 A EV charger | 60 A | 4 AWG | 6 AWG |
These are for short runs at normal temperatures. Use the calculator for your length, and the appliance's manual for its breaker.
Before anything is energized
A wire that is too small for its breaker can overheat inside a wall without tripping anything. This calculator applies the NEC as written for typical conditions, but local amendments, hot attics, bundled cables, conduit fill and the equipment's own instructions can require a larger wire. Most jurisdictions require a permit for new circuits. Have a licensed electrician confirm the wire, breaker and terminations.
Common questions, worked out
- What size breaker for an electric dryer?
- What size breaker for an electric range?
- What size breaker for an EV charger?
- What size breaker for an electric water heater?
- What size wire for a 20 amp breaker?
- What size wire for a 30 amp breaker?
- What size wire for a 40 amp breaker?
- What size wire for a 50 amp breaker?
- What size wire for a 60 amp breaker?
Questions
What size wire for a 50 amp breaker?
6 AWG copper NM-B (rated 55 A at 60°C), or 8 AWG copper THHN in conduit where every terminal is rated 75°C (50 A). Long runs need more. See the worked answer.
What size wire for a 30 amp breaker?
10 AWG copper. NEC 240.4(D) limits 10 AWG to a 30 A breaker, and 12 AWG to 20 A.
Can I use aluminum wire?
For feeders and large circuits, yes, with AL-rated lugs and antioxidant compound, torqued to spec. Aluminum branch circuits in small sizes were a fire problem in the 1960s and 70s; we don't suggest aluminum below 6 AWG.
Why does the EV charger need a bigger breaker than its amps?
EV charging is a continuous load, running three hours or more, so the NEC requires the circuit to be rated 125% of the charger's current. A 48 A charger needs a 60 A breaker.
Sources
Method checked 2026-11-26. Full formulas on the methodology page.