Methodology
How each calculator turns your inputs into a size, with every table and constant it uses. All the arithmetic lives in one file, engines.js, which this page and the calculators share.
Rules we follow
- Physics and published public methods first: federal test procedures (DOE, ENERGY STAR), state codes, and the National Electrical Code's ampacity values.
- Show the working. Every result lists the numbers that produced it.
- Round to the next standard size, and warn when the next size is far above the need.
- Where a licensed person must decide (wiring, septic permits, whole-house HVAC), say so on the result.
Climate zones and design temperatures
Heating and cooling loads are calculated at a design temperature: the outdoor temperature that is colder (heating, 99th percentile) or hotter (cooling, 1st percentile) than all but a few hours a year. The calculators use typical values for each IECC climate zone, from a representative city. For your county's exact values, use the ENERGY STAR Design Temperature Limit Reference Guide and enter them under "More inputs".
| Zone | Heating design | Cooling design | Summer moisture | Winter cold water |
|---|---|---|---|---|
| Zone 1, hot humid (Miami, Honolulu) | 47°F | 91°F | 50 gr/lb | 72°F |
| Zone 7, very cold (Duluth, Fargo) | -19°F | 84°F | 15 gr/lb | 37°F |
| Zone 8, subarctic (Fairbanks) | -40°F | 80°F | 5 gr/lb | 35°F |
| Zone 2A, hot humid (Houston, Orlando, New Orleans) | 33°F | 95°F | 50 gr/lb | 64°F |
| Zone 2B, hot dry (Phoenix, Tucson) | 38°F | 108°F | 0 gr/lb | 62°F |
| Zone 3A, warm humid (Atlanta, Dallas, Charlotte) | 24°F | 94°F | 40 gr/lb | 58°F |
| Zone 3B, warm dry (Las Vegas, Fresno, El Paso) | 30°F | 106°F | 0 gr/lb | 56°F |
| Zone 3C, marine (Los Angeles, San Francisco) | 42°F | 86°F | 10 gr/lb | 58°F |
| Zone 4A, mixed humid (Washington DC, St. Louis, Nashville, New York City) | 15°F | 92°F | 35 gr/lb | 52°F |
| Zone 4B, mixed dry (Albuquerque, Amarillo) | 18°F | 94°F | 0 gr/lb | 50°F |
| Zone 4C, marine (Seattle, Portland) | 26°F | 86°F | 10 gr/lb | 50°F |
| Zone 5A, cool humid (Chicago, Boston, Pittsburgh) | 0°F | 89°F | 30 gr/lb | 45°F |
| Zone 5B, cool dry (Denver, Salt Lake City, Reno) | 3°F | 93°F | 0 gr/lb | 45°F |
| Zone 6A, cold humid (Minneapolis, Milwaukee, Burlington) | -10°F | 88°F | 25 gr/lb | 40°F |
| Zone 6B, cold dry (Helena, Casper) | -10°F | 90°F | 0 gr/lb | 40°F |
Default zone by state
Choosing a state sets the zone where most of its people live. Many states span two or three zones (mountains, coast, north and south), so change it if yours differs.
Alabama 3A · Alaska 7 · Arizona 2B · Arkansas 3A · California 3C · Colorado 5B · Connecticut 5A · Delaware 4A · District of Columbia 4A · Florida 2A · Georgia 3A · Hawaii 1 · Idaho 5B · Illinois 5A · Indiana 5A · Iowa 5A · Kansas 4A · Kentucky 4A · Louisiana 2A · Maine 6A · Maryland 4A · Massachusetts 5A · Michigan 5A · Minnesota 6A · Mississippi 3A · Missouri 4A · Montana 6B · Nebraska 5A · Nevada 3B · New Hampshire 6A · New Jersey 4A · New Mexico 4B · New York 4A · North Carolina 4A · North Dakota 6A · Ohio 5A · Oklahoma 3A · Oregon 4C · Pennsylvania 5A · Rhode Island 5A · South Carolina 3A · South Dakota 6A · Tennessee 4A · Texas 2A · Utah 5B · Vermont 6A · Virginia 4A · Washington 4C · West Virginia 5A · Wisconsin 6A · Wyoming 6B
Heating and cooling loads (AC, heat pump, furnace, mini-split, BTU)
A simplified block load: the house is treated as one box with the floor area, height and window share you enter. It follows the same physics as ACCA Manual J but with typical construction values instead of a room-by-room takeoff, so it is an estimate, not a Manual J.
Heat loss = Σ(U × area) × (70°F − heating design temperature) + 1.08 × infiltration CFM × the same difference. Floors over a crawlspace or slab count at half the temperature difference.
Heat gain adds walls at the design difference + 10°F, ceilings at + 40°F for attic sun, windows by conduction plus area × SHGC × 55 Btu/h·ft², 230 Btu/h per person and 1,200 Btu/h of appliances. Summer infiltration runs at half the winter rate. The latent (humidity) load is 0.68 × CFM × the moisture difference, plus 200 Btu/h per person.
Ducts in an attic or crawlspace add 15% to heating and 20% to cooling.
We pick the smallest standard size at or above 95% of the load. Cooling equipment above 115% of the load (125% for heat pumps) gets a warning, following ACCA Manual S guidance, and so does furnace output above 140% of heat loss.
For heat pumps, output at the design temperature comes from typical extended-performance data: cold-climate variable-speed units keep about 78% of rated output at 5°F, standard units about 60% at 17°F. The shortfall becomes backup heat in kW (÷ 3,412).
| Construction | Wall U | Ceiling U | Window U | Window SHGC | Air changes/h |
|---|---|---|---|---|---|
| Little insulation (most homes before 1970, unimproved) | 0.2 | 0.1 | 0.9 | 0.8 | 0.65 |
| Average (1970s–1990s, or older and upgraded) | 0.09 | 0.05 | 0.5 | 0.65 | 0.4 |
| Good (built to 2006+ code) | 0.065 | 0.03 | 0.32 | 0.35 | 0.25 |
| High performance (2018+ code, spray foam, triple pane) | 0.045 | 0.02 | 0.25 | 0.28 | 0.12 |
Dehumidifiers
The AHAM sizing chart below is in the pints-per-day rating used until 2019. In 2019 the DOE moved the capacity test from 80°F to 65°F, which cut the label number by roughly 30% for the same machine; we divide by 1.4 to convert. Basements and crawlspaces go one size class up because air below 65°F holds less water and the coil frosts.
| Condition | 500 sq ft | 1,000 | 1,500 | 2,000 | 2,500 |
|---|---|---|---|---|---|
| Moderate | 10 | 14 | 18 | 22 | 26 |
| Very | 12 | 17 | 22 | 27 | 32 |
| Wet | 14 | 20 | 26 | 32 | 38 |
| Extreme | 16 | 23 | 30 | 37 | 44 |
Generators and battery backup
Generators: required capacity = the running watts of everything on at once + the start-up surge of the single largest motor (its starting minus running watts). Motors don't start in the same second, so adding every starting wattage, as some manufacturer calculators do, oversizes the generator. Portable generators get 10% headroom on running watts; standby generators are rated on propane, with about 10% less on natural gas.
Batteries: energy = Σ(running watts × hours powered × share of time the compressor or pump runs), divided by 0.85 for inverter loss and usable depth. The battery must also deliver the running total continuously and the surge for a moment.
| Appliance | Running W | Starting W | Volts |
|---|---|---|---|
| Refrigerator | 700 | 2,200 | 120 |
| Chest or upright freezer | 500 | 1,500 | 120 |
| 1/3 hp sump pump | 800 | 1,300 | 120 |
| 1/2 hp sump pump | 1,050 | 2,150 | 120 |
| 1 hp well pump | 2,000 | 4,000 | 240 |
| 3/4 hp well pump | 1,500 | 3,000 | 240 |
| Gas furnace blower (1/2 hp) | 875 | 2,350 | 120 |
| Gas boiler (pump + controls) | 300 | 600 | 120 |
| 10,000 Btu/h window AC | 1,200 | 3,600 | 120 |
| 3-ton central AC | 3,500 | 10,500 | 240 |
| 3-ton central AC with a soft starter | 3,500 | 5,500 | 240 |
| 3-ton heat pump (no backup strips) | 3,800 | 11,000 | 240 |
| 20 LED bulbs | 200 | 200 | 120 |
| TV + streaming box | 250 | 250 | 120 |
| Modem + router | 30 | 30 | 120 |
| Laptop or desktop | 250 | 250 | 120 |
| Phone chargers | 50 | 50 | 120 |
| 1,000 W microwave | 1,000 | 1,000 | 120 |
| Coffee maker | 1,000 | 1,000 | 120 |
| CPAP machine | 60 | 60 | 120 |
| 1/2 hp garage door opener | 875 | 2,350 | 120 |
| Washing machine | 1,150 | 2,250 | 120 |
| Gas dryer | 700 | 1,800 | 120 |
| Electric dryer | 5,400 | 6,750 | 240 |
| Electric water heater | 4,500 | 4,500 | 240 |
| One electric range burner | 1,500 | 1,500 | 240 |
| Space heater | 1,500 | 1,500 | 120 |
| 32 A EV charger | 7,700 | 7,700 | 240 |
| 13,500 Btu/h RV air conditioner | 1,500 | 2,900 | 120 |
| RV fridge on electric | 400 | 600 | 120 |
| Dishwasher | 1,500 | 1,500 | 120 |
Typical values compiled from DOE appliance energy guidance and manufacturers' published wattage tables. The nameplate on your appliance is better.
Water heaters
Tank heaters are sized by first-hour rating (FHR), the DOE-tested gallons a heater delivers in a busy hour, printed on the EnergyGuide label. Peak-hour demand = showers × minutes × flow × 70% hot + 20 gal per bath + 6 per dishwasher load + 7 per warm wash + 4 for sinks; we add 20% for winter inlet water.
Tankless heaters are sized by flow and temperature rise. Gas input (Btu/h) = gpm × 500 × rise ÷ 0.95. Electric kW = gpm × rise × 500 ÷ 3,412 ÷ 0.99; current = kW × 1,000 ÷ 240 V. The rise is your setpoint minus the zone's winter cold-water temperature.
Propane tanks
Two checks, and the larger tank wins. Fills: usable gallons per delivery are 60% of the tank (filled to 80%, refilled at 20%), times the deliveries a year you want. Vaporization: a tank must boil off enough gas for every appliance at once on the coldest night. We use the industry rule capacity (Btu/h) ≈ diameter × length (inches) × 70 at 30% full and 0°F, scaled by the temperature above propane's −44°F boiling point.
Well pressure tanks and pumps
Drawdown needed = pump gpm × minimum run time (1 minute, 1.5 above 10 gpm). The usable share of a tank follows Boyle's law: 1 − (cut-in + 14.7) ÷ (cut-out + 14.7), with the air precharge 2 psi below cut-in. Total dynamic head = water depth + elevation + cut-out psi × 2.31 + friction; pump horsepower ≈ gpm × head ÷ (3,960 × 45% efficiency).
Sump pumps
Inflow is best measured: pit area ÷ 231 gives gallons per inch of rise. The pump should move 1.5 × inflow at its total head (vertical lift + 1 ft per 10 ft of discharge pipe + 2 ft for fittings), read from typical submersible pump curves.
Septic tanks
Codes size tanks by bedrooms. These state minimums were read from the rule text; other states use the common minimum and are marked as such.
| State | 1–2 BR | 3 BR | 4 BR | 5 BR | Each extra | Rule |
|---|---|---|---|---|---|---|
| Washington | 900 | 900 | 1,000 | 1,250 | +250 | WAC 246-272A-0232 |
| Nevada | 1,000 | 1,000 | 1,200 | 1,500 | +150 | NAC 444.8306 |
| Minnesota | 1,000 | 1,000 | 1,500 | 1,500 | +250 | Minn. R. 7080.1930 |
| Virginia | 750 | 900 | 1,200 | 1,500 | +300 | 12VAC5-610-815 |
| Georgia | 1,000 | 1,000 | 1,000 | 1,250 | +250 | Georgia DPH Manual for On-Site Sewage Management Systems |
| Other states | 1,000 | 1,000 | 1,250 | 1,500 | +250 | common minimum (EPA Onsite Manual; many states) |
Water softeners
Grains per day = compensated hardness (gpg, plus 5 per ppm of iron) × people × gallons per person. Grains between regenerations = daily × days. We pick a softener whose rating at maximum salt is at least that ÷ 0.75, so it can run at an efficient salt dose. mg/L ÷ 17.1 = gpg.
Wire and breaker sizes
The breaker comes from the appliance (typical values, or the nameplate MOCP you enter) or from the load: continuous loads such as EV chargers and water heaters × 125%. The wire is the smallest size whose ampacity, in the temperature column the wiring method allows, is at least the breaker rating. NM-B (Romex) and UF cable use the 60°C column; conductors in conduit and SER cable use 75°C only where every terminal is rated 75°C. Small conductors are capped by NEC 240.4(D): 14 AWG copper 15 A, 12 AWG 20 A, 10 AWG 30 A. We never suggest aluminum smaller than 6 AWG.
Voltage drop = 2 × K × amps × one-way feet ÷ circular mils (K = 12.9 copper, 21.2 aluminum). It is computed at the nameplate current for appliances and continuous loads, and at 80% of the rating for a general circuit sized by amps. If it exceeds 3%, the wire goes up a size. Equipment grounds follow NEC Table 250.122.
| AWG | Copper 60°C | Copper 75°C | Aluminum 60°C | Aluminum 75°C |
|---|---|---|---|---|
| 1 | 110 A | 130 A | 85 A | 100 A |
| 2 | 95 A | 115 A | 75 A | 90 A |
| 3 | 85 A | 100 A | 65 A | 75 A |
| 4 | 70 A | 85 A | 55 A | 65 A |
| 6 | 55 A | 65 A | 40 A | 50 A |
| 8 | 40 A | 50 A | 35 A | 40 A |
| 10 | 30 A | 35 A | 25 A | 30 A |
| 12 | 20 A | 25 A | 15 A | 20 A |
| 14 | 15 A | 20 A | – | – |
| 250 | 215 A | 255 A | 170 A | 205 A |
| 300 | 240 A | 285 A | 195 A | 230 A |
| 350 | 260 A | 310 A | 210 A | 250 A |
| 1/0 | 125 A | 150 A | 100 A | 120 A |
| 2/0 | 145 A | 175 A | 115 A | 135 A |
| 3/0 | 165 A | 200 A | 130 A | 155 A |
| 4/0 | 195 A | 230 A | 150 A | 180 A |
Ampacity values per NEC 2023 Table 310.16 (30°C ambient, not more than three current-carrying conductors). Derate for hot attics, bundling and more conductors. A licensed electrician should confirm any circuit before it is energized.
Main sources
- ENERGY STAR, Design Temperature Limit Reference Guide (county design temperatures).
- U.S. DOE, Building America Guide to Determining Climate Regions by County; IECC 2021 climate zone map.
- U.S. DOE Energy Saver: sizing a new water heater; 10 CFR 430 test procedures for water heaters and dehumidifiers.
- ENERGY STAR and AHAM dehumidifier sizing guidance.
- NFPA 70 (National Electrical Code) 2023: Tables 310.16 and 250.122, sections 240.4(D), 210.19, 422.13, 625.42.
- State septic rules: WAC 246-272A-0232, NAC 444.8306, Minn. R. 7080.1930, 12VAC5-610-815, Georgia DPH on-site manual; U.S. EPA Onsite Wastewater Treatment Systems Manual.
- Propane: Rego LP-Gas Serviceman's Manual vaporization rule; NFPA 58.
- ACCA Manual J and Manual S (8th ed.) for the method our simplified load follows. We do not reproduce their tables.