All calculators / Heating & cooling
What size heat pump do I need?
A heat pump has to be big enough on the coldest night, when it puts out the least heat. This calculator checks that, not just summer cooling.
Replacing an old unit? Check how old it is first.
3-ton cold‑climate heat pump
Heating load 33,300 Btu/h at 15°F, cooling load 32,300 Btu/h. A 3-ton cold-climate heat pump puts out about 32,000 Btu/h on the design night, 96% of the heat loss; a 5 kW backup strip covers the coldest hours.
- This is an estimate, not an ACCA Manual J. Ask the installer for a Manual J and the model's output at your design temperature.
How we got there
| Heating design temperature | 15°F | 55°F below a 70°F room |
|---|---|---|
| Heat loss: walls | 5,600 Btu/h | |
| Heat loss: ceiling | 5,500 Btu/h | |
| Heat loss: floor | 3,300 Btu/h | |
| Heat loss: windows | 8,250 Btu/h | |
| Heat loss: air | 6,340 Btu/h | |
| Heat loss: ducts | 4,350 Btu/h | in an unconditioned attic or crawlspace |
| Heating load | 33,300 Btu/h | at the design temperature |
| Cooling design temperature | 92°F | 17°F above a 75°F room |
| Heat gain: walls | 2,750 Btu/h | |
| Heat gain: ceiling | 5,700 Btu/h | |
| Heat gain: windows | 13,280 Btu/h | conduction + sun through glass |
| Heat gain: people | 920 Btu/h | |
| Heat gain: appliances | 1,200 Btu/h | |
| Heat gain: air | 980 Btu/h | |
| Heat gain: humidity (latent) | 2,070 Btu/h | |
| Heat gain: ducts | 5,380 Btu/h | in an unconditioned attic or crawlspace |
| Cooling load | 32,300 Btu/h | 2.7 tons |
| Heat pump type | Cold-climate (variable speed) | |
| Output at 15°F | 89% of rated | typical; check the model's extended-performance table |
| Recommended size | 3 tons (36,000 Btu/h rated) | cooling 112% of load |
| Heat output at 15°F | 32,000 Btu/h | vs 33,300 Btu/h needed |
| Backup heat needed | 5 kW electric strips | or keep the furnace as backup (dual fuel) |
What to look for
- 3-ton variable-speed heat pump that keeps most of its output at your design temperature
- Look for: listed on the NEEP cold-climate heat pump list (if winters go below 20°F)
- Examples: Mitsubishi Hyper-Heat (H2i), Carrier Infinity 24VNA6 / Greenspeed, Bosch IDS 2.0, Daikin Fit
Examples only, not endorsements: model names checked 2026-11-26. Confirm the exact capacity on the spec sheet before you buy. We earn nothing from these.
Heating is the hard part
An air-source heat pump's output falls as the outdoor air gets colder, while the house loses heat faster. A standard unit rated at 36,000 Btu/h may put out 20,000 at 17°F. Cold-climate models keep 75 to 100% of their rating at 5°F.
So in cold climates the heating load usually sets the size, and in hot climates the cooling load does. The calculator works out both and picks a size that covers cooling without going far over it, then shows how much of the heating it covers on the design night. The gap becomes backup heat: electric strips in the air handler, or a gas furnace in a dual-fuel setup.
What to ask for when you get quotes
- The model's output at your heating design temperature, from its extended-performance table, not just the rated tons.
- Whether it is on the NEEP cold-climate heat pump list, if winters go below about 20°F.
- How much backup heat is installed, in kW, and the circuit it needs.
- A room-by-room Manual J for the whole house.
Replace or repair?
A heat pump older than about 12 to 15 years is near the end of its life. The build date is in the serial number on the rating plate. Find out how old your current unit is on Serial Age Finder, then size the replacement here.
Questions
Should I size the heat pump for heating or cooling?
For both. In cold climates size so the heat pump covers most of the heating load at the design temperature, but use a variable-speed unit so it can run slowly in summer instead of short-cycling. In warm climates cooling sets the size and heating is easy.
How much backup heat do I need?
The heating load at the design temperature minus what the heat pump puts out then, divided by 3,412 to get kW. The calculator shows it. A 10 kW strip heater needs a 60 A circuit.
Can a heat pump heat my house at 0°F?
A cold-climate model can, at reduced output. Look up the model's capacity at 5°F in its extended-performance data or on the NEEP list.
Sources
Method checked 2026-11-26. Full formulas on the methodology page.