What size pressure tank do I need for my well?
A pressure tank's job is to keep the pump from starting too often. The size depends on your pump's flow and the pressure switch setting, not the number of people.
44-gallon pressure tank
At 10 gpm the pump should run at least 1 minute, so the tank must hold 10.0 gallons of drawdown. At 40/60 psi only 27% of a tank is usable, so you need about 37 gallons total: a 44-gallon tank.
- Tank labels list drawdown at 20/40, 30/50 and 40/60. Use the drawdown at your switch setting, not the total gallons.
How we got there
| Pump flow | 10 gpm | typical for 2 bathrooms |
|---|---|---|
| Minimum pump run time | 1 min | to protect the motor |
| Drawdown needed | 10.0 gal | 10 gpm × 1 min |
| Pressure switch | 40/60 psi | precharge 38 psi |
| Share of tank that is usable | 27% | Boyle's law at this setting |
| Tank size needed | 37 gal total | |
| Total dynamic head | 326 ft | lift 150 ft + 60 psi × 2.31 + friction |
| Pump size | 2 hp | at 10 gpm (approx., use the pump curve) |
What to look for
- 44-gallon (total) pre-charged diaphragm or bladder tank; check its drawdown at your switch setting
- Examples: Amtrol Well-X-Trol, Flexcon Flexlite, Water Worker
Examples only, not endorsements: model names checked 2026-11-26. Confirm the exact capacity on the spec sheet before you buy. We earn nothing from these.
Drawdown, not tank gallons
A pressure tank holds a cushion of air above a bladder. When a tap opens, the air pushes water out until pressure falls to the cut-in setting and the pump starts. The water delivered between cut-out and cut-in is the drawdown. Only a fraction of the tank's volume is usable: at 40/60 psi, about 27%. That follows from Boyle's law, and it is why a "44-gallon" tank delivers about 12 gallons.
Pump makers want each start followed by at least a minute of running, so the motor cools. Drawdown needed = pump gpm × minimum run time. Divide by the usable share at your switch setting to get the tank size.
Pump size
The pump has to lift water from the pumping level, push it up to the house, overcome pipe friction, and reach the cut-out pressure (each psi is 2.31 ft of head). The calculator estimates horsepower from that total head and the flow at a typical 45% efficiency. For a real choice, read the pump curve: the model must deliver your flow at your total head.
Questions
What size pressure tank for 10 gpm?
At 40/60 psi and a 1-minute minimum run, a 10 gpm pump needs 10 gallons of drawdown, which takes about a 37-gallon tank. A 44-gallon tank has about 12 gallons of drawdown at that setting; check the drawdown column on the label.
What should the tank's air pressure be?
2 psi below the cut-in pressure, set with the tank empty and the pump off: 38 psi for a 40/60 switch, 28 for 30/50.