What size AC unit for 1,200 square feet?

2-ton central AC

Your estimated cooling load is 21,500 Btu/h (1.8 tons) for 1,200 sq ft in Zone 4A. Anything from 1.5 to 2 tons fits; 2 tons is the nearest standard size.

Assumes a 1,200 sq ft one-story house with average insulation, ducts in the attic, 15% windows, climate zone 4A. Change the inputs.

1,200 sq ft by climate (average insulation)

ClimateAnswer
Zone 2A, hot humid (Houston)2-ton central AC
Zone 2B, hot dry (Phoenix)2.5-ton central AC
Zone 3A, warm humid (Atlanta)2-ton central AC
Zone 4A, mixed (Washington DC)2-ton central AC
Zone 5A, cool (Chicago)2-ton central AC
Zone 4A, little insulation3-ton central AC
Zone 4A, built to 2006+ code1.5-ton central AC

Usually 1.5 to 2 tons

The 500 sq ft per ton rule says 2.4 tons for 1,200 sq ft. Most 1,200 sq ft homes need 1.5 to 2 tons; only hot, sunny, poorly insulated ones need 2.5. Small houses are where oversizing is most common, because the smallest standard condensers (1.5 tons) are already big for a tight one. If the calculator lands between sizes, an inverter (variable-speed) unit handles it better than a single-stage one.

Run it for your house

The calculator below starts from the assumptions above. Change any input and the answer updates.

More inputs

Calculated in your browser. Nothing you enter leaves this page.

2-ton central AC

Your estimated cooling load is 21,500 Btu/h (1.8 tons) for 1,200 sq ft in Zone 4A. Anything from 1.5 to 2 tons fits; 2 tons is the nearest standard size.

  • This is an estimate, not an ACCA Manual J. For a whole-house system, ask the installer for a room-by-room Manual J before you sign.

How we got there

Cooling design temperature92°F17°F above a 75°F room
Heat gain: walls2,260 Btu/h
Heat gain: ceiling3,420 Btu/h
Heat gain: windows7,970 Btu/hconduction + sun through glass
Heat gain: people920 Btu/h
Heat gain: appliances1,200 Btu/h
Heat gain: air590 Btu/h
Heat gain: humidity (latent)1,560 Btu/h
Heat gain: ducts3,580 Btu/hin an unconditioned attic or crawlspace
Cooling load21,500 Btu/h1.8 tons
Recommended size2 tons (24,000 Btu/h)112% of the load

What to look for

  • Any 2-ton condenser matched to its coil (AHRI-matched); 15.2+ SEER2 in the South, 13.4+ SEER2 in the North
  • Examples: Goodman GLXS4BA, Carrier Performance 24SPA5, Trane XR16, Rheem RA16

Examples only, not endorsements: model names checked 2026-11-26. Confirm the exact capacity on the spec sheet before you buy. We earn nothing from these.

Questions

Is 2 tons enough for 1,200 sq ft?

In most climates, yes. In a hot-dry climate with west windows and attic ducts, check with the calculator: it may say 2.5.

Sources