How Big Do I Need

All calculators / AC size calculator

What size AC unit for 2,000 square feet?

3-ton central AC

Your estimated cooling load is 32,300 Btu/h (2.7 tons) for 2,000 sq ft in Zone 4A. Anything from 2.5 to 3 tons fits; 3 tons is the nearest standard size.

Assumes a 2,000 sq ft one-story house with average insulation, ducts in the attic, 15% windows, climate zone 4A. Change the inputs.

2,000 sq ft by climate zone (average insulation)

ClimateAnswer
Zone 2A, hot humid (Houston)3-ton central AC
Zone 2B, hot dry (Phoenix)3.5-ton central AC
Zone 3A, warm humid (Atlanta)3-ton central AC
Zone 4A, mixed (Washington DC)3-ton central AC
Zone 5A, cool (Chicago)2.5-ton central AC
Zone 6A, cold (Minneapolis)2.5-ton central AC

Why the answer ranges from 2.5 to 3 tons and beyond

The rule of thumb says 500 sq ft per ton, so 2,000 sq ft would be 4 tons. That rule fits a leaky 1970s house in Texas. A 2,000 sq ft house built to the current code in a mixed climate usually needs 2.5 to 3 tons, and a hot-dry desert house more.

The table holds the house the same and changes only the climate. Insulation, windows and duct location move the answer as much again; the calculator below takes all of them.

Run it for your house

The calculator below starts from the assumptions above. Change any input and the answer updates.

More inputs

Calculated in your browser. Nothing you enter leaves this page.

3-ton central AC

Your estimated cooling load is 32,300 Btu/h (2.7 tons) for 2,000 sq ft in Zone 4A. Anything from 2.5 to 3 tons fits; 3 tons is the nearest standard size.

  • This is an estimate, not an ACCA Manual J. For a whole-house system, ask the installer for a room-by-room Manual J before you sign.

How we got there

Cooling design temperature92°F17°F above a 75°F room
Heat gain: walls2,750 Btu/h
Heat gain: ceiling5,700 Btu/h
Heat gain: windows13,280 Btu/hconduction + sun through glass
Heat gain: people920 Btu/h
Heat gain: appliances1,200 Btu/h
Heat gain: air980 Btu/h
Heat gain: humidity (latent)2,070 Btu/h
Heat gain: ducts5,380 Btu/hin an unconditioned attic or crawlspace
Cooling load32,300 Btu/h2.7 tons
Recommended size3 tons (36,000 Btu/h)112% of the load

What to look for

  • Any 3-ton condenser matched to its coil (AHRI-matched); 15.2+ SEER2 in the South, 13.4+ SEER2 in the North
  • Examples: Goodman GLXS4BA, Carrier Performance 24SPA5, Trane XR16, Rheem RA16

Examples only, not endorsements: model names checked 2026-11-26. Confirm the exact capacity on the spec sheet before you buy. We earn nothing from these.

Questions

Is 4 tons too big for 2,000 sq ft?

Often, yes, unless the house is old, leaky and in a hot climate. An oversized unit short-cycles and leaves the house clammy. Get a Manual J from the installer.

What about a two-story house?

Two stories with the same total area have less roof and more wall per square foot; the load is often slightly lower, but the upstairs runs hotter. Set floors to 2 in the calculator.

Sources

Checked 2026-11-26. Full method on the methodology page.