How Big Do I Need

All calculators / Mini-split size calculator

What size mini-split for 1,000 square feet?

15,000 Btu/h mini-split

This 1,000 sq ft room needs about 13,300 Btu/h of cooling and 14,500 Btu/h of heat at 15°F. A 15,000 Btu/h (1.25-ton) unit is the nearest standard size.

Assumes 1,000 sq ft of open space with average insulation, about 90 ft of outside wall, 15% windows, heating and cooling, zone 4A. Change the inputs.

1,000 sq ft by climate

ClimateAnswer
Zone 2A, hot humid (Houston)15,000 Btu/h mini-split
Zone 2B, hot dry (Phoenix)18,000 Btu/h mini-split
Zone 3A, warm humid (Atlanta)15,000 Btu/h mini-split
Zone 4A, mixed (Washington DC)15,000 Btu/h mini-split
Zone 5A, cool (Chicago)15,000 Btu/h mini-split
Zone 6A, cold (Minneapolis)18,000 Btu/h mini-split

One head or two

A single 18,000 to 24,000 Btu/h head can heat and cool 1,000 sq ft if it is mostly one open space. Heat doesn't travel well through doorways, so a 1,000 sq ft apartment with two closed bedrooms usually works better as a multi-zone system: a larger head in the living area and small 6,000 to 9,000 Btu/h heads in the bedrooms, or a small ducted unit.

Run it for your house

The calculator below starts from the assumptions above. Change any input and the answer updates.

More inputs

Calculated in your browser. Nothing you enter leaves this page.

15,000 Btu/h mini-split

This 1,000 sq ft room needs about 13,300 Btu/h of cooling and 14,500 Btu/h of heat at 15°F. A 15,000 Btu/h (1.25-ton) unit is the nearest standard size.

  • Heating on the design night needs 14,500 Btu/h. Pick a hyper-heat / cold-climate model rated near full output at 15°F, or keep other heat in the room.

How we got there

Heating design temperature15°F55°F below a 70°F room
Heat loss: walls2,820 Btu/h
Heat loss: ceiling2,750 Btu/h
Heat loss: floor1,650 Btu/h
Heat loss: windows4,130 Btu/h
Heat loss: air3,170 Btu/h
Heating load14,500 Btu/hat the design temperature
Cooling design temperature92°F17°F above a 75°F room
Heat gain: walls1,390 Btu/h
Heat gain: ceiling2,850 Btu/h
Heat gain: windows6,640 Btu/hconduction + sun through glass
Heat gain: people460 Btu/h
Heat gain: appliances400 Btu/h
Heat gain: air490 Btu/h
Heat gain: humidity (latent)1,030 Btu/h
Cooling load13,300 Btu/h1.1 tons
Recommended size15,000 Btu/h1.25 tons

What to look for

  • Single-zone 15,000 Btu/h ductless heat pump
  • DIY pre-charged: MRCOOL DIY 4th/5th Gen, Pioneer WYS/Diamante
  • Installed, cold climate: Mitsubishi M-Series Hyper-Heat (MSZ-FS / GL), Fujitsu Halcyon XLTH, Daikin Aurora

Examples only, not endorsements: model names checked 2026-11-26. Confirm the exact capacity on the spec sheet before you buy. We earn nothing from these.

Questions

How many BTU for 1,000 sq ft?

Typically 15,000 to 24,000 Btu/h depending on climate, insulation and whether you heat with it. The table shows each zone.

Sources

Checked 2026-11-26. Full method on the methodology page.