All calculators / Mini-split size calculator
What size mini-split for a 2-car garage?
12,000 Btu/h mini-split
This 576 sq ft garage needs about 9,900 Btu/h of cooling and 14,900 Btu/h of heat at 15°F. A 12,000 Btu/h (1.00-ton) unit is the nearest standard size.
Assumes a 24 × 24 ft (576 sq ft) attached garage with three outside walls (72 ft), little insulation, heating and cooling, zone 4A. Change the inputs.
Two-car garage by climate and insulation
| Garage | Answer |
|---|---|
| Uninsulated, zone 3A | 12,000 Btu/h mini-split |
| Uninsulated, zone 4A | 12,000 Btu/h mini-split |
| Uninsulated, zone 5A | 15,000 Btu/h mini-split |
| Insulated, zone 4A | 6,000 Btu/h mini-split |
| Insulated, zone 5A | 9,000 Btu/h mini-split |
| Insulated, zone 6A | 9,000 Btu/h mini-split |
Insulate first
A garage door is a large, thin, leaky wall, and the slab and walls are often bare. Heating an uninsulated garage to 65°F in a cold climate can take twice the mini-split an insulated one needs. Insulating the door, sealing its edges and insulating the ceiling usually drops the size by one or two steps, and saves money every winter.
Run it for your house
The calculator below starts from the assumptions above. Change any input and the answer updates.
12,000 Btu/h mini-split
This 576 sq ft garage needs about 9,900 Btu/h of cooling and 14,900 Btu/h of heat at 15°F. A 12,000 Btu/h (1.00-ton) unit is the nearest standard size.
- Heating on the design night needs 14,900 Btu/h. Pick a hyper-heat / cold-climate model rated near full output at 15°F, or keep other heat in the room.
- Garages lose far more heat than rooms. Insulating the door and ceiling often drops the size one step.
How we got there
| Heating design temperature | 15°F | 55°F below a 70°F room |
|---|---|---|
| Heat loss: walls | 6,080 Btu/h | |
| Heat loss: ceiling | 3,170 Btu/h | |
| Heat loss: floor | 1,580 Btu/h | |
| Heat loss: windows | 1,140 Btu/h | |
| Heat loss: air | 2,970 Btu/h | |
| Heating load | 14,900 Btu/h | at the design temperature |
| Cooling design temperature | 92°F | 17°F above a 75°F room |
| Heat gain: walls | 2,990 Btu/h | |
| Heat gain: ceiling | 3,280 Btu/h | |
| Heat gain: windows | 1,370 Btu/h | conduction + sun through glass |
| Heat gain: people | 460 Btu/h | |
| Heat gain: appliances | 400 Btu/h | |
| Heat gain: air | 460 Btu/h | |
| Heat gain: humidity (latent) | 990 Btu/h | |
| Cooling load | 9,900 Btu/h | 0.8 tons |
| Recommended size | 12,000 Btu/h | 1.00 tons |
What to look for
- Single-zone 12,000 Btu/h ductless heat pump
- DIY pre-charged: MRCOOL DIY 4th/5th Gen, Pioneer WYS/Diamante
- Installed, cold climate: Mitsubishi M-Series Hyper-Heat (MSZ-FS / GL), Fujitsu Halcyon XLTH, Daikin Aurora
Examples only, not endorsements: model names checked 2026-11-26. Confirm the exact capacity on the spec sheet before you buy. We earn nothing from these.
Questions
Is 12,000 BTU enough for a 2-car garage?
For an insulated garage in a mixed climate, usually. For an uninsulated garage you want heated in a cold winter, expect 18,000 to 24,000 Btu/h.
Can I run a mini-split on 120 V in a garage?
Some 9,000 and 12,000 Btu/h models run on 120 V. Larger ones need 240 V.