What size mini split for 400 square feet?
6,000 Btu/h mini-split
This 400 sq ft room needs about 6,100 Btu/h of cooling and 6,000 Btu/h of heat at 15°F. A 6,000 Btu/h (0.50-ton) unit is the nearest standard size.
Assumes a 400 sq ft room with average insulation, about 40 ft of outside wall, 15% windows, heating and cooling, zone 4A. Change the inputs.
400 sq ft by climate
| Climate | Answer |
|---|---|
| Zone 2A, hot humid (Houston) | 9,000 Btu/h mini-split |
| Zone 2B, hot dry (Phoenix) | 9,000 Btu/h mini-split |
| Zone 3A, warm humid (Atlanta) | 9,000 Btu/h mini-split |
| Zone 4A, mixed (Washington DC) | 6,000 Btu/h mini-split |
| Zone 5A, cool (Chicago) | 6,000 Btu/h mini-split |
| Zone 6A, cold (Minneapolis) | 9,000 Btu/h mini-split |
| Zone 4A, full afternoon sun | 9,000 Btu/h mini-split |
| Zone 4A, built to 2006+ code | 6,000 Btu/h mini-split |
Why charts give a bigger number
At 20 to 25 Btu per square foot, a chart puts 400 sq ft at 8,000 to 10,000 Btu/h. That rule ignores how many outside walls the room has, its windows and your climate. The table holds the room the same and changes one thing at a time. Heating usually sets the size north of zone 4; sun on west windows sets it in the South.
Run it for your house
The calculator below starts from the assumptions above. Change any input and the answer updates.
6,000 Btu/h mini-split
This 400 sq ft room needs about 6,100 Btu/h of cooling and 6,000 Btu/h of heat at 15°F. A 6,000 Btu/h (0.50-ton) unit is the nearest standard size.
- Heating on the design night needs 6,000 Btu/h. Pick a hyper-heat / cold-climate model rated near full output at 15°F, or keep other heat in the room.
How we got there
| Heating design temperature | 15°F | 55°F below a 70°F room |
|---|---|---|
| Heat loss: walls | 1,290 Btu/h | |
| Heat loss: ceiling | 1,100 Btu/h | |
| Heat loss: floor | 660 Btu/h | |
| Heat loss: windows | 1,650 Btu/h | |
| Heat loss: air | 1,270 Btu/h | |
| Heating load | 6,000 Btu/h | at the design temperature |
| Cooling design temperature | 92°F | 17°F above a 75°F room |
| Heat gain: walls | 630 Btu/h | |
| Heat gain: ceiling | 1,140 Btu/h | |
| Heat gain: windows | 2,660 Btu/h | conduction + sun through glass |
| Heat gain: people | 460 Btu/h | |
| Heat gain: appliances | 400 Btu/h | |
| Heat gain: air | 200 Btu/h | |
| Heat gain: humidity (latent) | 650 Btu/h | |
| Cooling load | 6,100 Btu/h | 0.5 tons |
| Recommended size | 6,000 Btu/h | 0.50 tons |
What to look for
- Single-zone 6,000 Btu/h ductless heat pump
- DIY pre-charged: MRCOOL DIY 4th/5th Gen, Pioneer WYS/Diamante
- Installed, cold climate: Mitsubishi M-Series Hyper-Heat (MSZ-FS / GL), Fujitsu Halcyon XLTH, Daikin Aurora
Examples only, not endorsements: model names checked 2026-11-26. Confirm the exact capacity on the spec sheet before you buy. We earn nothing from these.
Questions
How many BTU for 400 square feet?
Typically 6,000 to 12,000 Btu/h depending on climate, insulation, sun and whether the mini split also heats the room.