What size wire for a 100 amp service?

2 AWG aluminum for a 100 A service

A 100 A main service to a house needs at least 2 AWG aluminum service-entrance conductors (NEC 310.12 sizes them at 83% of the rating), with an 8 AWG copper grounding electrode conductor.

Assumes a 100 A main service to a single-family house, aluminum service-entrance cable, a 50 ft run from meter to panel. Change the inputs.

100 amp service wire

Conductor and runAnswer
Aluminum, 25 ft2 AWG aluminum for a 100 A service
Aluminum, 100 ft2 AWG aluminum for a 100 A service
Aluminum, 200 ft1/0 AWG aluminum for a 100 A service
Copper, 25 ft4 AWG copper for a 100 A service
Copper, 100 ft4 AWG copper for a 100 A service
For comparison: 100 A subpanel feeder, aluminum1 AWG aluminum feeder, 100 A breaker

Service conductors only. A subpanel fed at the same rating needs the full ampacity: see the subpanel pages.

The 83% rule

A house never draws its whole service rating for long, so NEC 310.12 lets the conductors of a single-family dwelling's main service be sized at 83% of the rating. For 100 A that means conductors rated at least 83 A: 4 AWG copper or 2 AWG aluminum in the 75°C column. That is where the familiar "2 AWG aluminum for 100 amps" comes from.

It applies only to the service or main feeder carrying the whole dwelling. A 100 A subpanel feeder needs conductors rated the full 100 A, which is one or two sizes larger; the last row of the table shows it.

Before anyone touches it

Service-entrance conductors run from the meter to the main panel with no breaker ahead of them. Replacing or upsizing them needs a permit, a licensed electrician, and usually the utility to pull the meter or disconnect the drop. The utility also sets the rules for its side of the meter. Treat this page as a way to check a quote, not as instructions.

Run it for your house

The calculator below starts from the assumptions above. Change any input and the answer updates.

Calculated in your browser. Nothing you enter leaves this page.

2 AWG aluminum for a 100 A service

A 100 A main service to a house needs at least 2 AWG aluminum service-entrance conductors (NEC 310.12 sizes them at 83% of the rating), with an 8 AWG copper grounding electrode conductor.

  • The 83% allowance is only for the service or main feeder that carries an entire single-family dwelling's load. A subpanel feeder needs the full rating.
  • The service drop or underground lateral up to the meter usually belongs to the utility and follows its rules. This size is for the service-entrance conductors from the meter to the main panel.
  • Service work needs a permit, a licensed electrician, and usually the utility to cut power. Service conductors have no breaker upstream: never work on them yourself.

How we got there

FeedsThe main service of a single-family homeNEC 310.12: conductors rated at least 83% of 100 A = 83 A
Circuit100 A circuit240 V
Load83.0 A
Breaker100 A double-polenext standard size up
Wire typeSER / feeder cable, 75°C terminals75°C ampacity column
Smallest wire for the breaker2 AWG aluminum90 A (NEC 310.16)
Voltage drop over 50 ft1.1%2.7 V at 83.0 A
Grounding electrode conductor8 AWG copperNEC Table 250.66, to the ground rods / water pipe

Questions

Can I use 2 AWG aluminum for a 100 amp service?

Yes, 2 AWG aluminum is the NEC 310.12 size for a 100 A single-family service in the 75°C column, if the meter base and main lugs are rated for aluminum. Long runs may need a size up for voltage drop.

What size ground rod wire?

The grounding electrode conductor to the ground rods follows NEC Table 250.66: 8 AWG copper for services up to 2 AWG copper or 1/0 aluminum, 4 AWG copper for 2/0 copper or 4/0 aluminum. Many inspectors accept 6 AWG copper to rods regardless.

Sources

Checked 2026-11-26. Full method on the methodology page.