How Big Do I Need

All calculators / Subpanel and service wire calculator

What size wire for a 100 amp subpanel?

1 AWG aluminum feeder, 100 A breaker

A 100 A subpanel feeder needs at least 1 AWG aluminum SER for a 50 ft run, with a 6 AWG ground.

Assumes a 100 A feeder breaker, aluminum SER cable with 75°C terminals, a 50 ft run. Change the inputs.

100 amp subpanel feeder by distance

Conductor and runAnswer
Aluminum, 25 ft1 AWG aluminum feeder, 100 A breaker
Aluminum, 100 ft1 AWG aluminum feeder, 100 A breaker
Aluminum, 150 ft1 AWG aluminum feeder, 100 A breaker
Aluminum, 250 ft2/0 AWG aluminum feeder, 100 A breaker
Copper, 50 ft3 AWG copper feeder, 100 A breaker
Copper, 150 ft3 AWG copper feeder, 100 A breaker

Not 2 AWG aluminum

You will see "2 AWG aluminum for 100 amps" in forums. That comes from NEC 310.12, which allows a smaller conductor for a dwelling's service or main feeder, because a whole house never draws its full rating. It does not apply to a subpanel feeder. A 100 A subpanel needs conductors rated 100 A: 1 AWG aluminum or 3 AWG copper at 75°C.

Four wires

A subpanel feeder has two hots, a neutral and a ground. In the subpanel the neutral bar stays isolated from the box and the ground bar is bonded to it. A subpanel in a detached garage or shop also needs its own ground rods and a disconnect. Have a licensed electrician confirm the feeder and grounding.

Run it for your house

The calculator below starts from the assumptions above. Change any input and the answer updates.

Calculated in your browser. Nothing you enter leaves this page.

1 AWG aluminum feeder, 100 A breaker

A 100 A subpanel feeder needs at least 1 AWG aluminum SER for a 50 ft run, with a 6 AWG ground.

  • Feeders to a subpanel need four wires (two hots, neutral, ground), and the neutral and ground must be separated in the subpanel.
  • A subpanel feeder uses the full 75°C ampacity. The 83% rule (NEC 310.12) applies only to the service or main feeder of a dwelling, not to subpanels.
  • The 75°C column only applies if the breaker, the appliance and every terminal are rated 75°C. NM-B (Romex) is always 60°C.
  • Aluminum: use AL-rated lugs, antioxidant paste, and torque to spec. We never suggest aluminum smaller than 6 AWG.
  • Wiring is a fire risk when it's wrong. Most places require a permit; have a licensed electrician confirm the wire, breaker and terminations before anything is energized.

How we got there

FeedsA subpanelfull 75°C ampacity; the 83% rule does not apply
Circuit100 A circuit240 V
Load100.0 A
Breaker100 A double-polenext standard size up
Wire typeSER / feeder cable, 75°C terminals75°C ampacity column
Smallest wire for the breaker1 AWG aluminum100 A (NEC 310.16)
Voltage drop over 50 ft0.8%2.0 V at 80.0 A
Equipment ground6 AWG aluminumNEC 250.122

Questions

Can I use 2 AWG aluminum for a 100 A subpanel?

Not under the NEC's ampacity table: 2 AWG aluminum is rated 90 A at 75°C, so it can feed a 90 A breaker. The 83% allowance in 310.12 is only for the main service of a dwelling.

What size for 100 amps at 200 ft?

Voltage drop pushes the size up, typically to 1/0 aluminum at that distance. The table above shows each step.

Sources

Checked 2026-11-26. Full method on the methodology page.