What size breaker for an electric range?

6 AWG copper on a 50 A breaker

An electric range on a 50 A breaker needs at least 6 AWG copper NM-B for a 50 ft run, with a 10 AWG ground.

Assumes an electric range on copper NM-B cable, a 50 ft run, typical nameplate values. Change the inputs.

Breaker and wire by setup

SetupAnswer
Range, 50 A6 AWG copper on a 50 A breaker
Cooktop, 40 A8 AWG copper on a 40 A breaker
Wall oven, 30 A10 AWG copper on a 30 A breaker
Range, 100 ft run6 AWG copper on a 50 A breaker

The rule

Freestanding electric ranges typically need a 40 or 50 A double-pole breaker; the install manual says which. A 50 A circuit with 6 AWG copper and a NEMA 14-50 receptacle covers nearly every range. Separate cooktops and wall ovens usually need less.

Check the nameplate

The appliance's install manual or nameplate lists the breaker it needs (sometimes as MOCP, maximum overcurrent protection). Where it differs from a typical value, the nameplate wins. Have a licensed electrician confirm the breaker, the wire and the receptacle before the circuit is energized.

Run it for your house

The calculator below starts from the assumptions above. Change any input and the answer updates.

More inputs

Calculated in your browser. Nothing you enter leaves this page.

6 AWG copper on a 50 A breaker

An electric range on a 50 A breaker needs at least 6 AWG copper NM-B for a 50 ft run, with a 10 AWG ground.

  • Appliance nameplates and install manuals set the breaker size (MOCP). Where they differ from this page, the nameplate wins.
  • Wiring is a fire risk when it's wrong. Most places require a permit; have a licensed electrician confirm the wire, breaker and terminations before anything is energized.

How we got there

CircuitElectric range240 V
Load40.0 A
Breaker50 A double-poletypical; use the nameplate or manual
Wire typeNM-B (Romex) cable60°C ampacity column
Smallest wire for the breaker6 AWG copper55 A (NEC 310.16)
Voltage drop over 50 ft0.8%2.0 V at 40.0 A
Equipment ground10 AWG copperNEC 250.122

Questions

Can I put a bigger breaker on the same wire?

No. The breaker protects the wire. A larger breaker on the same wire lets it overheat without tripping.

Does it need GFCI protection?

Under the 2023 NEC, 240 V receptacles for dryers and ranges, and EV charger outlets, generally need GFCI protection. Hardwired units vary. Ask your electrician what your jurisdiction has adopted.

Sources