All calculators / Wire and breaker size calculator
What size breaker for an electric range?
6 AWG copper on a 50 A breaker
An electric range on a 50 A breaker needs at least 6 AWG copper NM-B for a 50 ft run, with a 10 AWG ground.
Assumes an electric range on copper NM-B cable, a 50 ft run, typical nameplate values. Change the inputs.
Breaker and wire by setup
| Setup | Answer |
|---|---|
| Range, 50 A | 6 AWG copper on a 50 A breaker |
| Cooktop, 40 A | 8 AWG copper on a 40 A breaker |
| Wall oven, 30 A | 10 AWG copper on a 30 A breaker |
| Range, 100 ft run | 6 AWG copper on a 50 A breaker |
The rule
Freestanding electric ranges typically need a 40 or 50 A double-pole breaker; the install manual says which. A 50 A circuit with 6 AWG copper and a NEMA 14-50 receptacle covers nearly every range. Separate cooktops and wall ovens usually need less.
Check the nameplate
The appliance's install manual or nameplate lists the breaker it needs (sometimes as MOCP, maximum overcurrent protection). Where it differs from a typical value, the nameplate wins. Have a licensed electrician confirm the breaker, the wire and the receptacle before the circuit is energized.
Run it for your house
The calculator below starts from the assumptions above. Change any input and the answer updates.
6 AWG copper on a 50 A breaker
An electric range on a 50 A breaker needs at least 6 AWG copper NM-B for a 50 ft run, with a 10 AWG ground.
- Appliance nameplates and install manuals set the breaker size (MOCP). Where they differ from this page, the nameplate wins.
- Wiring is a fire risk when it's wrong. Most places require a permit; have a licensed electrician confirm the wire, breaker and terminations before anything is energized.
How we got there
| Circuit | Electric range | 240 V |
|---|---|---|
| Load | 40.0 A | |
| Breaker | 50 A double-pole | typical; use the nameplate or manual |
| Wire type | NM-B (Romex) cable | 60°C ampacity column |
| Smallest wire for the breaker | 6 AWG copper | 55 A (NEC 310.16) |
| Voltage drop over 50 ft | 0.8% | 2.0 V at 40.0 A |
| Equipment ground | 10 AWG copper | NEC 250.122 |
What to look for
Examples only, not endorsements: model names checked 2026-11-26. Confirm the exact capacity on the spec sheet before you buy. We earn nothing from these.
Questions
Can I put a bigger breaker on the same wire?
No. The breaker protects the wire. A larger breaker on the same wire lets it overheat without tripping.
Does it need GFCI protection?
Under the 2023 NEC, 240 V receptacles for dryers and ranges, and EV charger outlets, generally need GFCI protection. Hardwired units vary. Ask your electrician what your jurisdiction has adopted.