All calculators / Wire and breaker size calculator
What size wire for a 40 amp breaker?
8 AWG copper on a 40 A breaker
A 40 A circuit needs at least 8 AWG copper NM-B for a 50 ft run, with a 10 AWG ground.
Assumes a 40 A circuit at 240 V in copper NM-B (Romex), a 50 ft run, non-continuous load. Change the inputs.
40 amp wire size by cable type and distance
| Cable and run | Answer |
|---|---|
| Copper NM-B, 25 ft | 8 AWG copper on a 40 A breaker |
| Copper NM-B, 100 ft | 8 AWG copper on a 40 A breaker |
| Copper NM-B, 150 ft | 6 AWG copper on a 40 A breaker |
| Copper THHN in conduit, 75°C, 50 ft | 8 AWG copper on a 40 A breaker |
| Copper UF-B buried, 100 ft | 8 AWG copper on a 40 A breaker |
The answer and why
8 AWG copper is the usual answer for 40 A. In NM-B cable it is rated 40 A at 60°C, exactly enough; 10 AWG is capped at 30 A by NEC 240.4(D) whatever the cable. On long runs the voltage drop rises, and above 3% the calculator goes up a size.
Typical uses for a 40 A circuit: a cooktop, a 32 A EV charger, or a small subpanel.
Before you wire it
This applies the NEC for typical conditions. Hot attics, bundled cables and local amendments can require a larger wire. New circuits usually need a permit; have a licensed electrician confirm the wire, breaker and terminations before the circuit is energized.
Run it for your house
The calculator below starts from the assumptions above. Change any input and the answer updates.
8 AWG copper on a 40 A breaker
A 40 A circuit needs at least 8 AWG copper NM-B for a 50 ft run, with a 10 AWG ground.
- Wiring is a fire risk when it's wrong. Most places require a permit; have a licensed electrician confirm the wire, breaker and terminations before anything is energized.
How we got there
| Circuit | 40 A circuit | 240 V |
|---|---|---|
| Load | 40.0 A | |
| Breaker | 40 A double-pole | next standard size up |
| Wire type | NM-B (Romex) cable | 60°C ampacity column |
| Smallest wire for the breaker | 8 AWG copper | 40 A (NEC 310.16) |
| Voltage drop over 50 ft | 1.0% | 2.5 V at 32.0 A |
| Equipment ground | 10 AWG copper | NEC 250.122 |
What to look for
Examples only, not endorsements: model names checked 2026-11-26. Confirm the exact capacity on the spec sheet before you buy. We earn nothing from these.
Questions
Can I use 10 AWG on a 40 amp breaker?
No. NEC 240.4(D) limits 10 AWG copper to a 30 A breaker and 14 AWG to 15 A.