What size wire for a 40 amp breaker?

8 AWG copper on a 40 A breaker

A 40 A circuit needs at least 8 AWG copper NM-B for a 50 ft run, with a 10 AWG ground.

Assumes a 40 A circuit at 240 V in copper NM-B (Romex), a 50 ft run, non-continuous load. Change the inputs.

40 amp wire size by cable type and distance

Cable and runAnswer
Copper NM-B, 25 ft8 AWG copper on a 40 A breaker
Copper NM-B, 100 ft8 AWG copper on a 40 A breaker
Copper NM-B, 150 ft6 AWG copper on a 40 A breaker
Copper THHN in conduit, 75°C, 50 ft8 AWG copper on a 40 A breaker
Copper UF-B buried, 100 ft8 AWG copper on a 40 A breaker

The answer and why

8 AWG copper is the usual answer for 40 A. In NM-B cable it is rated 40 A at 60°C, exactly enough; 10 AWG is capped at 30 A by NEC 240.4(D) whatever the cable. On long runs the voltage drop rises, and above 3% the calculator goes up a size.

Typical uses for a 40 A circuit: a cooktop, a 32 A EV charger, or a small subpanel.

Before you wire it

This applies the NEC for typical conditions. Hot attics, bundled cables and local amendments can require a larger wire. New circuits usually need a permit; have a licensed electrician confirm the wire, breaker and terminations before the circuit is energized.

Run it for your house

The calculator below starts from the assumptions above. Change any input and the answer updates.

More inputs

Calculated in your browser. Nothing you enter leaves this page.

8 AWG copper on a 40 A breaker

A 40 A circuit needs at least 8 AWG copper NM-B for a 50 ft run, with a 10 AWG ground.

  • Wiring is a fire risk when it's wrong. Most places require a permit; have a licensed electrician confirm the wire, breaker and terminations before anything is energized.

How we got there

Circuit40 A circuit240 V
Load40.0 A
Breaker40 A double-polenext standard size up
Wire typeNM-B (Romex) cable60°C ampacity column
Smallest wire for the breaker8 AWG copper40 A (NEC 310.16)
Voltage drop over 50 ft1.0%2.5 V at 32.0 A
Equipment ground10 AWG copperNEC 250.122

Questions

Can I use 10 AWG on a 40 amp breaker?

No. NEC 240.4(D) limits 10 AWG copper to a 30 A breaker and 14 AWG to 15 A.