All calculators / Wire and breaker size calculator
What size wire for a 20 amp breaker?
12 AWG copper on a 20 A breaker
A 20 A circuit needs at least 12 AWG copper NM-B for a 50 ft run, with a 12 AWG ground.
Assumes a 20 A circuit at 120 V in copper NM-B (Romex), a 50 ft run, non-continuous load. Change the inputs.
20 amp wire size by cable type and distance
| Cable and run | Answer |
|---|---|
| Copper NM-B, 25 ft | 12 AWG copper on a 20 A breaker |
| Copper NM-B, 100 ft | 8 AWG copper on a 20 A breaker |
| Copper NM-B, 150 ft | 6 AWG copper on a 20 A breaker |
| Copper THHN in conduit, 75°C, 50 ft | 12 AWG copper on a 20 A breaker |
| Copper UF-B buried, 100 ft | 8 AWG copper on a 20 A breaker |
The answer and why
12 AWG copper is the answer for 20 A. NEC 240.4(D) caps 14 AWG at 15 A, so a 20 A breaker on 14 AWG wire is a code violation and a fire risk even though the table rates 14 AWG higher. On long runs the voltage drop rises, and above 3% the calculator goes up a size.
Typical uses for a 20 A circuit: kitchen, bathroom and laundry outlets, a dishwasher, or a 120 V window AC.
Before you wire it
This applies the NEC for typical conditions. Hot attics, bundled cables and local amendments can require a larger wire. New circuits usually need a permit; have a licensed electrician confirm the wire, breaker and terminations before the circuit is energized.
Run it for your house
The calculator below starts from the assumptions above. Change any input and the answer updates.
12 AWG copper on a 20 A breaker
A 20 A circuit needs at least 12 AWG copper NM-B for a 50 ft run, with a 12 AWG ground.
- Wiring is a fire risk when it's wrong. Most places require a permit; have a licensed electrician confirm the wire, breaker and terminations before anything is energized.
How we got there
| Circuit | 20 A circuit | 120 V |
|---|---|---|
| Load | 20.0 A | |
| Breaker | 20 A | next standard size up |
| Wire type | NM-B (Romex) cable | 60°C ampacity column |
| Smallest wire for the breaker | 12 AWG copper | 20 A (NEC 310.16, 240.4(D)) |
| Voltage drop over 50 ft | 2.6% | 3.2 V at 16.0 A |
| Equipment ground | 12 AWG copper | NEC 250.122 |
What to look for
Examples only, not endorsements: model names checked 2026-11-26. Confirm the exact capacity on the spec sheet before you buy. We earn nothing from these.
Questions
Can I use 14 AWG on a 20 amp breaker?
No. NEC 240.4(D) limits 10 AWG copper to a 30 A breaker and 14 AWG to 15 A.
Sources
Checked 2026-11-26. Full method on the methodology page.