How Big Do I Need

All calculators / Wire and breaker size calculator

What size wire for a 20 amp breaker?

12 AWG copper on a 20 A breaker

A 20 A circuit needs at least 12 AWG copper NM-B for a 50 ft run, with a 12 AWG ground.

Assumes a 20 A circuit at 120 V in copper NM-B (Romex), a 50 ft run, non-continuous load. Change the inputs.

20 amp wire size by cable type and distance

Cable and runAnswer
Copper NM-B, 25 ft12 AWG copper on a 20 A breaker
Copper NM-B, 100 ft8 AWG copper on a 20 A breaker
Copper NM-B, 150 ft6 AWG copper on a 20 A breaker
Copper THHN in conduit, 75°C, 50 ft12 AWG copper on a 20 A breaker
Copper UF-B buried, 100 ft8 AWG copper on a 20 A breaker

The answer and why

12 AWG copper is the answer for 20 A. NEC 240.4(D) caps 14 AWG at 15 A, so a 20 A breaker on 14 AWG wire is a code violation and a fire risk even though the table rates 14 AWG higher. On long runs the voltage drop rises, and above 3% the calculator goes up a size.

Typical uses for a 20 A circuit: kitchen, bathroom and laundry outlets, a dishwasher, or a 120 V window AC.

Before you wire it

This applies the NEC for typical conditions. Hot attics, bundled cables and local amendments can require a larger wire. New circuits usually need a permit; have a licensed electrician confirm the wire, breaker and terminations before the circuit is energized.

Run it for your house

The calculator below starts from the assumptions above. Change any input and the answer updates.

More inputs

Calculated in your browser. Nothing you enter leaves this page.

12 AWG copper on a 20 A breaker

A 20 A circuit needs at least 12 AWG copper NM-B for a 50 ft run, with a 12 AWG ground.

  • Wiring is a fire risk when it's wrong. Most places require a permit; have a licensed electrician confirm the wire, breaker and terminations before anything is energized.

How we got there

Circuit20 A circuit120 V
Load20.0 A
Breaker20 Anext standard size up
Wire typeNM-B (Romex) cable60°C ampacity column
Smallest wire for the breaker12 AWG copper20 A (NEC 310.16, 240.4(D))
Voltage drop over 50 ft2.6%3.2 V at 16.0 A
Equipment ground12 AWG copperNEC 250.122

Questions

Can I use 14 AWG on a 20 amp breaker?

No. NEC 240.4(D) limits 10 AWG copper to a 30 A breaker and 14 AWG to 15 A.