What size breaker for an electric water heater?

10 AWG copper on a 30 A breaker

A 4,500 W electric tank water heater on a 30 A breaker needs at least 10 AWG copper NM-B for a 50 ft run, with a 10 AWG ground.

Assumes an electric water heater on copper NM-B cable, a 50 ft run, typical nameplate values. Change the inputs.

Breaker and wire by setup

SetupAnswer
4,500 W tank10 AWG copper on a 30 A breaker
5,500 W tank10 AWG copper on a 30 A breaker

The rule

A standard 4,500 W tank heater draws 18.75 A at 240 V. NEC 422.13 treats it as a continuous load, so the circuit must be rated 125%: 23.4 A, which rounds to a 30 A breaker with 10 AWG copper.

Check the nameplate

The appliance's install manual or nameplate lists the breaker it needs (sometimes as MOCP, maximum overcurrent protection). Where it differs from a typical value, the nameplate wins. Have a licensed electrician confirm the breaker, the wire and the receptacle before the circuit is energized.

Run it for your house

The calculator below starts from the assumptions above. Change any input and the answer updates.

More inputs

Calculated in your browser. Nothing you enter leaves this page.

10 AWG copper on a 30 A breaker

A 4,500 W electric tank water heater on a 30 A breaker needs at least 10 AWG copper NM-B for a 50 ft run, with a 10 AWG ground.

  • Appliance nameplates and install manuals set the breaker size (MOCP). Where they differ from this page, the nameplate wins.
  • Wiring is a fire risk when it's wrong. Most places require a permit; have a licensed electrician confirm the wire, breaker and terminations before anything is energized.

How we got there

Circuit4,500 W electric tank water heater240 V, continuous load
Load18.8 A× 125% = 23.4 A (continuous)
Breaker30 A double-poletypical; use the nameplate or manual
Wire typeNM-B (Romex) cable60°C ampacity column
Smallest wire for the breaker10 AWG copper30 A (NEC 310.16, 240.4(D))
Voltage drop over 50 ft1.0%2.3 V at 18.8 A
Equipment ground10 AWG copperNEC 250.122

Questions

Can I put a bigger breaker on the same wire?

No. The breaker protects the wire. A larger breaker on the same wire lets it overheat without tripping.

Does it need GFCI protection?

Under the 2023 NEC, 240 V receptacles for dryers and ranges, and EV charger outlets, generally need GFCI protection. Hardwired units vary. Ask your electrician what your jurisdiction has adopted.