What size wire for a 50 amp breaker?
6 AWG copper on a 50 A breaker
A 50 A circuit needs at least 6 AWG copper NM-B for a 50 ft run, with a 10 AWG ground.
Assumes a 50 A, 240 V circuit in copper NM-B (Romex) cable, a 50 ft run, non-continuous load. Change the inputs.
50 amp wire size by cable type and distance
| Cable and run | Answer |
|---|---|
| Copper NM-B, 25 ft | 6 AWG copper on a 50 A breaker |
| Copper NM-B, 100 ft | 6 AWG copper on a 50 A breaker |
| Copper NM-B, 150 ft | 6 AWG copper on a 50 A breaker |
| Copper THHN in conduit, 75°C, 50 ft | 8 AWG copper on a 50 A breaker |
| Copper THHN in conduit, 75°C, 150 ft | 6 AWG copper on a 50 A breaker |
| Aluminum, 75°C, 50 ft | 6 AWG aluminum on a 50 A breaker |
| Copper UF-B buried, 100 ft | 6 AWG copper on a 50 A breaker |
Continuous loads (EV charging, heaters) must be sized at 125%: a 40 A charger needs a 50 A circuit.
Why the answer depends on the cable
NM-B (Romex) and UF cable are limited to the 60°C column of NEC Table 310.16, even though the wires inside are rated 90°C. Single conductors in conduit (THHN/THWN) can use the 75°C column when the breaker and the equipment terminals are rated 75°C, so they can be one size smaller for the same 50 A breaker.
Distance matters too. Over a long run the wire's resistance drops the voltage; above 3% we go up a size. That is why the table shows larger wire for 100 and 150 ft runs.
Typical uses for a 50 A circuit: a range, welder, 50 A RV outlet or EV charger. The appliance's install manual sets the breaker; size the wire from that.
Before you wire it
This page applies the NEC for typical conditions. Hot attics, cables bundled together, conduit with more than three current-carrying wires, and local amendments can all require a larger wire. New circuits usually need a permit. Have a licensed electrician confirm the wire, breaker and terminations before the circuit is energized.
Run it for your house
The calculator below starts from the assumptions above. Change any input and the answer updates.
6 AWG copper on a 50 A breaker
A 50 A circuit needs at least 6 AWG copper NM-B for a 50 ft run, with a 10 AWG ground.
- Wiring is a fire risk when it's wrong. Most places require a permit; have a licensed electrician confirm the wire, breaker and terminations before anything is energized.
How we got there
| Circuit | 50 A circuit | 240 V |
|---|---|---|
| Load | 50.0 A | |
| Breaker | 50 A double-pole | next standard size up |
| Wire type | NM-B (Romex) cable | 60°C ampacity column |
| Smallest wire for the breaker | 6 AWG copper | 55 A (NEC 310.16) |
| Voltage drop over 50 ft | 0.8% | 2.0 V at 40.0 A |
| Equipment ground | 10 AWG copper | NEC 250.122 |
What to look for
Examples only, not endorsements: model names checked 2026-11-26. Confirm the exact capacity on the spec sheet before you buy. We earn nothing from these.
Questions
Can I use 8 AWG for 50 amps?
8 AWG copper is allowed on a 50 A breaker only as individual THHN conductors in conduit with 75°C-rated terminals (50 A). In NM-B cable 8 AWG is limited to 40 A, so use 6 AWG.
What size ground wire?
NEC Table 250.122 sets the equipment ground by breaker size: 10 AWG copper for 30 to 60 A circuits, 8 AWG aluminum.